Schneider Korea Sanhe EOCR-FMZ2-WRCUW motor protector
Schneider Korea Sanhe EOCR-FMZ2-WRCUW motor protector built-in microprocessor unit real-time process / high-precision Schneider South Korea three and EOCR-FMZ2-WRCUW motor protector Pvc Elbow,Sewage Pvc Elbow,Sewage Pvc Coupling,Sewage Pvc Plug Zhejiang Huangyan Minghua Plastic Pipe Fitting CO.,LTD , https://www.pipefitting-mh.com
Sanhe EOCR Co., Ltd. is Korea's largest manufacturer of motor protectors. The company was founded in 1981 by Dr. Jin Renxi (CEO of Schneider Electric Group Korea).
In 2001, in order to develop the company into a global, strategic enterprise, he joined the Schneider Electric Group of France.
EOCR's main products are electronic motor protection relays, electronic overcurrent relays, electronic undercurrent relays, electronic undervoltage relays, other protection and monitoring devices, and current transformers.
â—† Built-in microprocessor unit â—† Real-time process/high precision â—† With over-temperature inverse time protection without external CT current within 32A â—† Communication method: Modbus/RS-485
â—† Enhanced monitoring function: communication transmission distance up to 400 meters, 3-phase current display, trip cause display â—† Current amplitude display bar, trip cause display, applicable to single-phase and three-phase motors
◆ Comply with the relevant provisions of the “Regulations on the Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment†RoHS
â—† For split products, normal protection is provided even if PDM is not connected
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn
EOCR-3MZ2/FMZ2 Protection Project Protection project Setting range and conditions Action time Overcurrent The load operating current (ln) exceeds the set overcurrent value (ls), ie ln≥ls
Setting range: 0.5~60A (Definite time limit - Def)
0.5~32A (inverse time limit - Inv, overheating inverse time limit - th) Time limit: 0.2~30 seconds optional inverse time limit and overheating inverse time limit: 1~30 level Undercurrent The load operating current (ln) is lower than the set overcurrent value (uc), ie ln ≤ uc
Undercurrent value setting cannot exceed or equal to overcurrent setting value OFF, adjustable from 1 to 10 seconds Stall This value is set to a multiple of the overcurrent setting value. It is suitable for the setting range during startup: 0.5~30A 2~8 times of the overcurrent setting value is more than 2~6 times of the 40A overcurrent setting value until 60A 2 to 4 times the current setting value 0.5 seconds after D-Time Stall This value is set to a multiple of the overcurrent set value. It is suitable for the setting range during operation: 1.5~5 times of 0.5~50A overcurrent setting value up to 1.5~4 times of 60A overcurrent setting value. Adjustable from 0.2 to 5 seconds Missing phase The maximum phase imbalance ratio of the three-phase current exceeds 85% (OFF/ON) OFF, adjustable from 0.5 to 5 seconds Reverse phase The phase sequence of the three-phase current is not reciprocal (OFF/ON) OFF, within 0.15 seconds Current imbalance Current imbalance rate = (maximum phase current - minimum phase current) / maximum phase current × 100%
Current imbalance rate ≥ set current imbalance rate setting range: 10~50% Adjustable from 1 to 10 seconds Ground Exceeding the setting ground current value setting range: OFF, 0.03~10A Adjustable from 0.05 to 10 seconds EOCR-3MZ2/FMZ2 technical parameters Current range Overcurrent Definite time: 0.5-60A, greater than 60A using external CT
Inverse time limit: 0.5-32A, about 32A using external CT Undercurrent 0.5A~OC set value Current-time characteristics Definite time limit, inverse time limit, overheating inverse time limit time setting Definite time limit D-time 0~200 seconds O-time 0.2~30 seconds Inverse time/overheating inverse time limit 1~30 level Ground delay time 0~30 seconds Grounding action time 0.05~10 seconds Automatic reset 0.5 seconds to 20 minutes Reset form Manual, electric, automatic Operating power supply Voltage 85~260VAC/DC (85%~110%), 24VAC/DC (±5%) frequency 50/60HZ Power consumption Less than 7VA display Seven-segment digital display Three-phase current value and leakage current cycle display, fault cause, setting parameters Current amplitude display stick The actual running current amplitude is displayed on the spot (65%~100%) communication Modbus/RS-485 Installation method switchboard Embedded panel surroundings temperature Storage -40°C~+85°C run -20°C~+60°C humidity No condensation state 30-85% RH insulation insulation Between the outer casing and the line Greater than DC500V 10 megohms Compressive strength Between the outer casing and the line 2KV 50/60Hz 1 minute Output contact 1KV 50/60Hz 1 minute Line room 2KV 50/60Hz 1 minute