Help the mall: S7-1200 uses the USS communication protocol to speed the MM440

When the S7-1200 uses the USS communication protocol to speed the MM440, the STEP7-Basic V10.5 software comes with the USS instruction library. Unlike the STEP7-Micro/WIN V4.0 software, an additional instruction library is required.
When the S7-1200 uses the USS communication protocol to speed the MM440, the STEP7-Basic V10.5 software comes with the USS instruction library. Unlike the STEP7-Micro/WIN V4.0 software, an additional instruction library is required.
USS protocol communication Each S7-1200 CPU can have up to 3 communication modules, and each CM1241 (RS485) communication module supports up to 16 inverters. Therefore, users can establish up to three USS networks in one S7-1200 CPU, and each USS network supports up to 16 inverters, for a total of up to 48 USS inverters.
Use a CPU1214C to perform USS stepless speed regulation on the MM440 inverter, change the parameter of P701 to 1, and read the P702 parameters. The technical parameters of the motor are known, the power is 0.06 kW, the rated speed is 1440 r/min, the rated voltage is 380 V, the rated current is 0.35 A, and the rated frequency is 50 Hz. Please propose a solution.
(1) Software and hardware configuration 11 sets of STEP7-Basic V10.5;
21 sets of MM440 inverters;
31 CPU1214C;
41 sets of CM1241 (RS485);
51 motors;
61 shielded twisted pairs.
The hardware configuration is shown in the figure.



(2) Setting of the inverter According to Table 3-12, setting the parameters of the inverter and setting the parameters of the inverter correctly are very important for USS communication.
Table 3-12 Inverter Parameter Table

Serial number

Inverter parameters

Factory default

Set value

Function Description

1

P0304

230

380

Motor rated voltage (380V)

2

P0305

3.25

035

Motor rated current (0.35A)

3

P0307

0 75

0.06

Motor rated power (60W)

4

P0310

50 00

50.00

Rated frequency of the motor (50Hz)

5

P0311

0

1440

Rated speed of the motor (1430 r/min)

6

P0700

2

5

Select command source (USS setting for COM link)

7

P1000

2

5

Frequency source (USS setting of COM link)

8

P2010

6

6

USS baud rate (6-9600)

9

P2011

0

1

Site address

10

P2012

2

2

USS PZD length

11

P2013

127

4

USS PKW length



Contact information:

Guangzhou Bang Electronic Commerce Co., Ltd.

Phone Contact: Miss Zhang

Fax work QQ: 3302646249

Help the mall:

Address: Building 1, Jin'an Creative Park, No. 582, Huangpu Avenue East, Tianhe District, Guangzhou
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

Dual Energy Luggage Scanner:

Dual energy Luggage Scanners are the tube voltage above 140kv, and the over-package image is imaged in color. The acquisition card has high energy and low energy. It can be switched at any time with the probe.

Energy-saving design: the machine can automatically sense the object, put the baggage on the machine to start running, no baggage, the machine is stationary.

Dynamic picture switching: the screen can be switched when it is still, and can be switched freely when it is dynamic.

Dual Energy Luggage Scanner

Dual Energy Luggage Scanner

Airport X Ray Scanner,X-Ray Inspection Machine,Baggage Scanner,Dual Energy Luggage Scanner

Shenzhen MCD Electronics Co., Ltd. , https://www.gdmcd.com